C.11 dpi diagnostic object – Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual

Page 165

Advertising
background image

EtherNet I/P Objects

C-29

C.11 DPI Diagnostic Object

Class Code

Instances

The number of instances depends on the maximum number of
diagnostic items in the device. The total number of diagnostic items
can be read in Instance 0, Attribute 2.

Class Attributes

Hexadecimal

Decimal

0x99

153

Instances (Hex.)

(Dec.)

Device

Example

Description

0x0000 – 0x3FFF 0 – 16383

Host

0

Class Attributes (Drive)

0x4000 – 0x43FF

16384 – 17407

Module

1

Drive Diagnostic Item 1

0x4400 – 0x47FF

17408 – 18431

DPI Port 1

2

Drive Diagnostic Item 2

0x4800 – 0x4BFF 18432 – 19455

DPI Port 2

0x4C00 – 0x4FFF

19456 – 20479

DPI Port 3

16384

Class Attributes (Module)

0x5000 – 0x53FF

20480 – 21503

DPI Port 4

16385

Module Diagnostic Item1

0x5400 – 0x57FF

21504 – 22527

DPI Port 5

0x5800 – 0x5BFF

22528 – 23551

DPI Port 6

Attribute

ID

Access

Rule

Name

Data Type

Description

1

Get

Class Revision WORD

1

2

Get

Number of
Instances

WORD

Number of diagnostic items in the
device

3

Get

ENUM Offset

WORD

DPI ENUM object instance offset