Module Parameters
B-11
Sets the percent scale factor for the Reference from the network.
Selects the destination in the drive of the Peer I/O input. The
module receives this data from the network and sends it to the drive.
Important: Changes to these parameters are ignored when module
parameter 47 (Peer Inp Enable) is On.
Important: If the parameter is set to input a logic command,
configure the mask in module parameter 40 (Peer Cmd
Mask) so that the desired bits from the Peer device are
used.
37
Ref Adjust
Range:
0.00 to 200.00 %
Default:
100.00 %
Type:
Read/Write
Reset Required: No
!
ATTENTION: Changes to module parameter 37 (Ref
Adjust) take effective immediately. A drive receiving its
Reference from the module will receive the newly
scaled Reference, resulting in change of speed.
Failure to observe this precaution could result in bodily
injury and/or damage to equipment.
38
39
Peer A Input
Peer B Input
Range:
0 = Off
1 = Cmd/Ref
2 = Datalink A Input
3 = Datalink B Input
4 = Datalink C Input
5 = Datalink D Input
Default:
0 = Off
Type:
Read/Write
Reset Required: No