Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual

Page 40

Advertising
background image

4-14

EtherNet/IP Communications Module

Step 2.

In module parameters 42 through 45 (Peer Inp Addr 1
through Peer Inp Addr 4), set the IP address of the node
from which you want to receive data. See figure 4.20.
Valid nodes must have EtherNet/IP modules connected to
drives with compatible logic command/status words.

Step 3.

Select the destination of the data that is input to the drive
as Peer A in module parameter 38 (Peer A Input). See
figure 4.21.

If you select a Reference or Datalink as an input, note the
following:

If a drive that uses a 32-bit Reference and 32-bit

Datalinks receives a 16-bit Reference or Datalink, it
uses the data in its most significant word, and its least
significant word is zero.

Figure 4.19 – Peer Input Enable Screen on an LCD OIM

Figure 4.20 – Peer Input Address 1 Screen on an LCD OIM

Figure 4.21 – Peer A Input Screen on an LCD OIM

Value Setting

0

Off (Default)

1

On

Port 5 Device

RECOMM-ENET

Parameter #: 47
Peer Inp Enable

0

Off

Port 5 Device

RECOMM-ENET

Parameter #: 42
Peer Inp Addr 1

0

0 <> 255

Default = 0.0.0.0

255 . 255 . 255 . 255

[Peer Inp Addr 1]

[Peer Inp Addr 2]

[Peer Inp Addr 3]

[Peer Inp Addr 4]

IP Address of Node Transmitting
Peer I/O

Port 5 Device

RECOMM-ENET

Parameter #: 38
Peer A Input

1

Cmd/Ref

Value

Description

0

Off (Default)

1

Logic Command/Reference

2 - 5

Datalink A, B, C, or D
Input