3-2

EtherNet/IP Communications Module

Set the Web Pages Switch (SW2) to enable or disable the module
web pages (see figure 3.1 and setting descriptions below). By
default, the module web pages are disabled. For complete details
on module web pages, see Chapter 9, View the module’s Web
Pages.

3.3

Connecting the Module to the Drive

Step 1.

Remove power from the drive.

Step 2.

Use static control precautions.

!

ATTENTION: The EtherNet/IP module contains
ESD- (Electrostatic Discharge) sensitive parts that
can be damaged if you do not follow ESD control
procedures. Static control precautions are required
when handling the module. Failure to observe these
precautions could result in damage to equipment.

SW2 Setting

Description

Down (OFF) position

Disables the module web pages (default
setting).

Up (ON) position

Enables the module web pages.

Figure 3.1 – Setting Web Pages Switch

!

ATTENTION: The Reliance Electric drive may
contain high voltages that can cause injury or death.
Remove power from the drive, and then verify power
has been discharged before installing or removing
an module . Failure to observe this precaution could
result in severe bodily injury or loss of life.

2

1

O

N

UNUSED

SWITCH

Disable Web
Position

Enable Web
Position

WEB PAGES