For example, an image that uses 32-bit words for Reference and
four Datalinks would change the I/O image in figure 6.1 as follows:

An image that uses a 16-bit Reference and 32-bit Datalinks would
change the I/O image in figure 6.1 as follows:

As another example, figure 6.2 illustrates an I/O image that does
not use all of the I/O data. Only the Logic Command/Reference and
Datalink B are enabled. In this example, the reference is a 32-bit
word, and Datalinks are 16-bit words.

Word

Output I/O

Word

Input I/O

0

Logic Command/Status

0 - 1

Pad Word

1

Pad Word

2

Logic Command/Status

2 - 3

Reference/Feedback

3

Pad Word

4 - 7

Datalink A1/A2

4 - 5

Reference/Feedback

8 - 11

Datalink B1/B2

6 - 9

Datalink A1/A2

12 - 15

Datalink C1/C2

11 - 13

Datalink B1/B2

16 - 19

Datalink D1/D2

14 - 17

Datalink C1/C2

18 - 21

Datalink D1/D2

Word

Output I/O

Word

Input I/O

0

Logic Command/Status

0 - 1

Pad Word

1

Pad Word

2

Logic Command/Status

2

Reference/Feedback

3

Pad Word

3

Pad Word

4 - 5

Reference/Feedback

4 - 7

Datalink A1/A2

6 - 9

Datalink A1/A2

8 - 11

Datalink B1/B2

11 - 13

Datalink B1/B2

12 - 15

Datalink C1/C2

14 - 17

Datalink C1/C2

16 - 19

Datalink D1/D2

18 - 21

Datalink D1/D2