5-6

EtherNet/IP Communications Module

Step 3.

Edit the fields listed in table 5.2.

Step 4.

Under Connection Parameters, edit the fields listed in
table 5.3.

Figure 5.8 – Module Properties Dialog Box - Page 1

SP600

Table 5.2 – Edit Module Properties

Field

Enter This Information

Name

A name to identify the module and drive.

Comm. Format Data - INT.

This setting formats the data in 16-bit words.

IP Address

The IP address of the module.

Table 5.3 – Edit Connection Parameters

Field

Assembly

Instance

Column

Size Column

Input

1 (This value is
required.)

The value will vary based on your
application (setting of parameters
23 (I/O Config) and 36 (M-S
Output) and the size (16- or 32-
bit) of the Reference/Feedback
and Datalinks in the drive. Refer to
tables 5.4 and 5.5.

Output

2 (This value is
required.)

The value will vary based on your
application (setting of Parameters
23 - [I/O Config] and 35 - [M-S
Input]) and the size (16- or 32-bit)
of the Reference/Feedback and
Datalinks in the drive. Refer to
tables 5.4 and 5.5.

Configuration

6 (This value is
required.)

0 (This value is required.)