C.8 DPI Parameter Object

Class Code

Instances

The number of instances depends on the number of parameters in
the device. The total number of parameters can be read in
Instance 0, Attribute 0.

Class Attributes

Hexadecimal

Decimal

0x93

147

Instances (Hex)

(Dec)

Device

Example

Description

0x0000-0x3FFF 0-16383

Host

0

Class Attributes (Drive)

0x4000-0x43FF

16384-17407 Module

1

Drive Parameter 1
Attributes

0x4400-0x47FF

17408-18431 DPI Port 1

2

Drive Parameter 2
Attributes

0x4800-0x4BFF 18432-19455 DPI Port 2

...

...

0x4C00-0x4FFF 19456-20479 DPI Port 3

16484

Class Attributes (Module)

0x5000-0x53FF

20480-21503 DPI Port 4

16385

Module Parameter 1
Attributes

0x5400-0x57FF

21504-22527 DPI Port 5

...

...

0x5800-0x5BFF 22528-23551 DPI Port 6

Attribute

ID

Access

Rule

Name

Data Type

Description

0

Get

Number of
Instances

WORD

Number of parameters in the device

1

Set

Write
Protect
Password

WORD

0 = Password disabled
n = Password

2

Set

NVS
Command
Write

BYTE

0 = No operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory

3

Get

NVS
Parameter
Value
Checksum

WORD

Checksum of all parameter values in a user
set in NVS