Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual

Page 38

Advertising
background image

4-12

EtherNet/IP Communications Module

4.8.2 Configuring the Module to Transmit Peer-to-

Peer Data

To configure an module to transmit Peer-to-Peer data:

Step 1.

Verify that module parameter 51 (Peer Out Enable) is set
to Off (see figure 4.15). This parameter must be Off while
you configure peer output parameters.

Step 2.

Select the source of the data to output to the network in
module parameter 49 (Peer A Output). See figure 4.16.

Step 3.

If desired, select an additional source of the data to output
to the network in module parameter 50 (Peer B Output) as
shown in figure 4.17.

Step 4.

Set module parameters 52 (Peer Out Time) and 53 (Peer
Out Skip) to establish the minimum and maximum
intervals between Peer messages. Because the module

Figure 4.15 – Peer Out Enable Screen on an LCD OIM

Figure 4.16 – Peer A Output Screen on an LCD OIM

Figure 4.17 – Peer B Output Screen on an LCD OIM

Value Setting

0

Off (Default)

1

On

Port 5 Device

RECOMM-ENET

Parameter #: 51
Peer Out Enable

0

Off

Port 5 Device

RECOMM-ENET

Parameter #: 49
Peer A Output

1

Cmd/Ref

Value

Description

0

Off (Default)

1

Logic Command/Reference

2 - 5

Datalink A, B, C, or D Input

6 - 9

Datalink A, B, C, or D Output

Port 5 Device

RECOMM-ENET

Parameter #: 50
Peer B Output

2

DL A Input

Value

Description

0

Off (Default)

1

Logic Command/Reference

2 - 5

Datalink A, B, C, or D
Input

6 - 9

Datalink A, B, C, or D
Output