Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual

Page 32

Advertising
background image

4-6

EtherNet/IP Communications Module

4.4

Using Parameters to Set the IP
Address, Subnet Mask, and Gateway
Address

By default, the module is configured so that you set its IP address,
subnet mask, and gateway address using a BOOTP server. If you
want to set these features using the module’s parameters instead,
you must disable BOOTP and then set the appropriate parameters
in the module.

To disable the BOOTP feature:

Step 1.

Set the value of module parameter 3 (BOOTP) to
Disabled as shown in figure 4.6.

Step 2.

Reset the module. Refer to Resetting the Module in
section 4.11.

After disabling the BOOTP feature, you can then configure the IP
address, subnet mask, and gateway using the module’s parameters.

To set an IP address using parameters:

Step 1.

Verify that module parameter 3 (BOOTP) is set to
Disabled. This parameter must be set to Disabled to
configure the IP address using parameters.

Step 2.

Set the value of module parameters 4 through 7 (IP Addr
Cfg 1 through IP Addr Cfg 4) to a unique IP address.

Figure 4.6 – Sample BOOTP Screen on an LCD OIM

Figure 4.7 – Sample IP Address Screen on an LCD OIM

Value Setting
0

Disabled

1

Enabled (Default)

Port 5 Device

RECOMM-ENET

Parameter #: 03
BOOTP

0

Disabled

Port 5 Device

RECOMM-ENET

Parameter #: 04
IP Addr Cfg 1

0

0 <> 255

Default = 0.0.0.0

255 . 255 . 255 . 255

[IP Addr Cfg 1]

[IP Addr Cfg 2]

[IP Addr Cfg 3]

[IP Addr Cfg 4]