C-30

EtherNet/IP Communications Module

Instance Attributes

Services

Attribute

ID

Access

Rule

Name

Data Type

Description

0

Get

Full/All Info

STRUCT of
BOOL[32]
CONTAINER

1

CONTAINER
CONTAINER
CONTAINER
WORD
WORD
STRING[4]
UINT
UINT
UINT
INT
DWORD
STRING[16]

Descriptor (Refer to pages C-24 to
C-25)
Value
Minimum value
Maximum value
Default value
Pad Word
Pad Word
Units (e.g., amp, Hz)
Multiplier

2

Divisor

2

Base

2

Offset

2

Link (source of the value) (0 = no link)
Always zero (0)
Parameter name

1

Get/Set Value

Various

Diagnostic item value

1

A CONTAINER is a 32-bit block of data that contains the data type used by a value.
If signed, the value is sign extended. Padding is used in the CONTAINER to ensure
that it is always 32-bits.

2

This value is used in the formulas used to convert the value between display units
and internal units. Refer to Formulas for Converting on page C-25.

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

Yes

Set_Attribute_Single