EtherNet I/P Objects

C-27

Services

C.10 DPI Alarm Object

Class Code

Products such as SP600, GV6000 and LiquiFlo 2.0 drives use this
object for alarms or warnings. Modules do not support this object.

Instances

The number of instances depends on the maximum number of
alarms supported by the queue. The maximum number of alarms
can be read in Instance 0, Attribute 2.

Class Attributes

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

Yes

Set_Attribute_Single

Hexadecimal

Decimal

0x98

152

Instances (Hex)

(Dec)

Device

Example

Description

0x0000-0x3FFF 0-16383

Host

0

Class Attributes (Drive)

Only host devices can have alarms.

1

Most Recent Alarm

2

Second Most Recent Alarm

Attribute

ID

Access

Rule

Name

Data Type

Description

1

Get

Class Revision WORD

Revision of object

2

Get

Number of
Instances

WORD

Maximum number of alarms that
the device can record in its queue

3

Set

Alarm
Command
Write

BYTE

0 = No Operation
1 = Clear Alarm
2 = Clear Alarm Queue
3 = Reset Device

4

Get

Fault Data List

STRUCT of
BYTE
BYTE
WORD[n]

Reserved

5

Get

Number of
Recorded
Alarms

WORD

Number of alarms in the queue. A
“0” indicates the alarm queue is
empty.

Advertising