Motion Control Theory

67

AMP-204C / AMP-208C

Figure 4-2: Control cycle

The motion program is executed in motion control cycle to control

jobs to be executed in each motion control cycle directly for more

precise completion of realtime jobs. Please pay attention to DSP

loading when doing this.
Loading of CPU in controller is hard to predict as the controller is

affected by many factors, e.g. external signals, user operations, and

algorithm process during its operations. In most cases, please try to

keep CPU utilization rate to below 70% and reserve 30% of CPU

capacity to the processing of system jobs and momentary work loads.
Overloading (work loads exceed control cycle) may lead to

unpredictable results. This controller provides you with some

functions and tools to monitor processor utilization rate and adjust

control procedures. In case of any processor overloading, the

controller logs and warns (interrupt, plase refer to section of interrupt)

that you may take for proper responses in your program.
How to use API:
get_motion_control_timing ()

// get usage amount of current motion

control cycle
get_max_ motion_control_timing

()// get maximum usage amount

of motion control cycle
get_motion_control_timing ()

// get usage amount of current host

control cycle
get_motion_control_timing ()

// get maximum usage amount of host

control cycle
reset_max_motion_control_timing()
reset_max_host_control_timing()
get_over_cycle_event()
get_over_cycle_count()
reset_over_cycle_count ()

Movement control
Elapsed time

System work
Elapsed time

Movement control
duration

System work duration

Time