Yaskawa GPD503 Drive User Manual

Page 102

Advertising
background image

ACTION

DESCRIPTION

DISPLAY

Press PRGM Key

DRIVE lamp lights. Display shows the

DRIVE

Frequency Reference value as set by

to Return to

input at terminal 13, 14, or 16, ref.

(no digit

Drive Mode

terminal 17.

blinking)

Set Auto/Manual

Display shows frequency reference

Switch, If Used,

commanded by the present level of the

To Select Desired

input signal.

(no digit

External

blinking)

Reference Signal

Adjust External

Observe display as speed reference is

Speed Reference

adjusted. Stop when display shows

To Desired Level

desired output frequency.

(no digit

EXAMPLE: Adjust for 60Hz output.

blinking)

Press DSPL Key

Present Output Frequency is

to Show Present

displayed.

Output Frequency

Close Contact

Check motor operation at programmed

at Terminals

Jog Frequency operating speed.

7 & 11 To
Jog Motor

Close Contact

GPD 503 output increases to Frequency

at Terminals 1

Reference level, at programmed Accel Rate.

& 11 To Perform

Motor speed increases accordingly.

Forward Run

Open Contact

Motor speed decreases under GPD 503

at Terminals 1

control, at preset Decel Rate, to zero.

& 11 To Stop
Drive

F 6 0.0 0

0.0 0

6.0 0

6 0.0 0

0.0 0

F 0 0.0 0

F 0 0.0 0

3-10

3.5 DRIVE MODE OPERATION Continued

C. Drive Operation (2-Wire Control) By External Input Signals - Continued: