2.26 SLIP COMPENSATION

bn-08: Slip Compensation Gain

Factory setting:

0.0

%

Range: 0.0 to 9.9 %

This constant sets the slip compensation gain, in increments of 0.1%. When the gain is
1.0, the output frequency is increased by 1% of the Cn-04 setting at rated current. A
setting of 0.0 results in no slip compensation.

Fref

Cn-14

Cn-15

+

+

+

400 Hz

SFS

SOFT STARTER

10% LIMITATION

bn-08

INTERNAL
FREQUENCY
REFERENCE

20%

K

CURRENT

DETECTOR

NOTE: When Fref is less than Cn-07 setting, this function is disabled.

Slip Compensation Block Diagram

2-41

EXAMPLE

:

Desired frequency is 45 Hz
Motor slip = 3% at full load

(bn-08 =

3.0

)

Actual output frequency at

full load = 46.35 Hz

V

f

46.35 Hz actual output

3% frequency
boost

corresponding
voltage boost

45 Hz command

Changed