1.4 ELECTRICAL INSTALLATION Continued

1.4.2 Control Circuit

All basic control circuit (signal) interconnections are shown in the appropriate diagram:

• Interconnections for external two-wire control in combination with the Digital

Operator are shown in Figure 1-3 (for 230V or 460V rated drives) and Figure
1-5 (for 575V rated drives).

• Interconnections for external three-wire control in combination with the Digital

Operator are shown in Figure 1-4 (for 230V or 460V rated drives) and Figure
1-6 (for 575V rated drives).

Make wiring connections according to Figures 1-1 thru 1-4 and Table 1-3, observing the
following :

• Signal Leads : Terminals 1-8, 11-17, and 21-27.

• Control Leads : Terminals 9 & 10 and 18-20.

• Power Leads : Input Terminals L1 (R), L2 (S), and L3 (T), and Output Terminals

T1 (U), T2 (V), and T3 (W).

• Use twisted shielded or twisted-pair shielded wire (20-14 AWG (0.5-2mm

2

)for

1-60HP (CT); 18-14 AWG (0.75-2mm

2

) for 75-400HP (CT) ) for control and signal

circuit leads. When using shielded wire, the shield sheath MUST be connected
at the GPD 503 ONLY (terminal 12). The other end should be dressed neatly and
left unconnected (floating). See Figure 1-1.

• Lead length should NOT EXCEED 164 feet (50 meters). Wire sizes should be

determined considering the voltage drop.

TO GPD 503
SIGNAL
TERMINALS

TO SHIELD
SHEATH
TERMINAL
(TERM. 12)

WRAP BOTH ENDS
OF SHEATH WITH
INSULATING TAPE

CRIMP
CONNECTION

SHIELD SHEATH

OUTER JACKET

DO NOT
CONNECT

TO
EXTERNAL
CIRCUIT

Figure 1-1. Shielded Sheath Termination

1-4