INDICATION

(DISPLAY)

FAILURE INDICATION ITEM

DESCRIPTION

ou

Overvoltage

Internal monitor of DC Bus voltage indicates that input

(blinking)

AC power is excessively high, while GPD 503 is in
stopped condition.

ou

Overvoltage (OV)

Detection level: Approx. 400V for 230V GPD 503;
Approx. 800V for 460V GPD 503 (700V if Cn-01 < 400);
Approx. 1000V for 575V GPD 503.
Reset level: 385V.

r r

Regenerative transistor

Dynamic Braking resistor has failed.

failure

r H

Braking resistor unit

Dynamic Braking resistor has overheated.

overheated

Uu

Low voltage (Power UV)

Internal monitor of DC Bus voltage indicates that input

(blinking)

AC power is below Undervoltage detection level, while the
GPD 503 is in stopped condition.

Uu1

Low voltage (Power UV)

Occurs two seconds after detection of low voltage.
(See "Undervoltage" specification, under "Protective
Functions", in Appendix 2.)

Uu2

Low voltage (Control UV)

Control circuit voltage levels drop below acceptable
levels during operation.

Uu3

Low voltage (MC-ANS fault)

Main circuit magnetic contactor does not
operate correctly.

Table 6-1. Failure Indication and Details - Continued

INDICATION

(DISPLAY) FAULT

DESCRIPTION