Yaskawa GPD503 Drive User Manual

Page 47

Advertising
background image

2.12 EXTERNAL FAULT INPUTS Continued

B. Sn-15 thru Sn-18: Multi-function

Data

20 - 2F

: External Fault 1 (terminal 5)

Inputs (Term. 5 thru 8)

Data

30 - 3F

: External Fault 2 (terminal 6)

Data

40 - 4F

: External Fault 3 (terminal 7)

Data

50 - 5F

: External Fault 4 (terminal 8)

The multi-function input terminals can be used to monitor external fault contacts. When
the External Fault 1-4 signals are inputted,

E F5

to

E F8

are displayed on the Digital

Operator (steady for a major fault situation, blinking for a minor fault situation). The
second digit of the Sn-15 thru Sn-18 setting is entered as a hexadecimal value; when
converted to its binary equivalent, it defines what type of external fault contact is used and
how the GPD 503 will react to the fault input.

Binary — 0 0 0 0

0 = N.O. contact
1 = N.C. contact

0 = always detected
1 = during operation

00 = ramp to stop
01 = coast to stop
10 = emergency stop
11 = continue operation

(minor fault)

EXAMPLE:

To program External Fault 1 (terminal 5)
for a N.C. contact, always detected, and
GPD 503 to continue operation, solve
for X:

Sn-15 data =

2 X

X = 1 1 0 1

N.C. contact

always detected

continue operation

= 1 1 0 1 (binary) = D (hex)

Sn-15 data =

2d

For the same type of input at External Fault 2 (terminal 6):

Sn-16 data =

3 d

BINARY TO HEX CONVERSION

BINARY

HEX

0 0 0 0

0

0 0 0 1

1

0 0 1 0

2

0 0 1 1

3

0 1 0 0

4

0 1 0 1

5

0 1 1 0

6

0 1 1 1

7

1 0 0 0

8

1 0 0 1

9

1 0 1 0

A

1 0 1 1

B *

1 1 0 0

C

1 1 0 1

D **

1 1 1 0

E

1 1 1 1

F

2-16

*

Appears as "

b

" on Digital Operator.

**

Appears as "

d

" on Digital Operator.