2.8 DC INJECTION BRAKING Continued

B. Cn-10: DC Inj. Braking Start Frequency

Range: 0.0 to 10.0 Hz

Cn-11: DC Inj.Braking Current

Factory setting:

50

%

(% of Drive Rated Current)

Range: 0 to 100 %

Cn-13: DC Injection Time at Start

Factory setting:

0.5

sec

Range: 0.0 to 25.5 sec

DC injection can be used to stop a motor whose rotational direction is uncertain at start-
up. For this operation, application of DC injection braking current is controlled by a
multi-function input (see paragraph 2.8.D).

With ramp to stop enabled (Sn-04 =

0 0

X X), after a STOP command is received the

GPD 503 controls motor deceleration according to the Decel Time setting, until output
frequency reaches the DC Injection Braking Start Frequency (Cn-10 setting). Then the
GPD 503 output is turned off and DC injection current is applied to the motor. The
effective DC injection time and current should be set to provide adequate stopping without
excessive motor heating. The DC injection voltage is determined by the DC injection
braking current and motor impedance.

DC Braking Sequence

RUN COMMAND

OUTPUT FREQUENCY

STOP

RAMP TO STOP

DC

DC

DC INJECTION TIME AT

START (Cn-13)

DC INJ. BRK. START

FREQUENCY (Cn-10)

DC INJECTION TIME AT

STOP (Cn-12)

2-10