2.7 CRITICAL FREQUENCY REJECTION

A. Cn-16: Prohibited Frequency 1

Factory setting (each):

0.0

Cn-17: Prohibited Frequency 2
Cn-18: Prohibited Frequency 3

Range (each): 0.0 to 400.0 Hz

These three constants allow programming of up to three prohibited frequency points for
eliminating problems with resonant vibration of the motor/machine. This feature does not
actually eliminate the selected frequency values, but will accelerate and decelerate the
motor through the prohibited bandwidth.

B. Cn-19: Prohibited Frequency Deadband

Factory setting:

1.0

Range: 0.0 to 25.5 Hz

This constant determines the width of the deadband around each selected prohibited
frequency point. The factory setting is

1.0

, which establishes a deadband of ±1.0 Hz.

EXAMPLE:

Vibration encountered between 30.0 and 36.0 Hz.

SOLUTION:

Set Cn-16 to

33.0. This is the center of the problem

frequency band.

Set Cn-19 to

3.0. This will cause the GPD 503 to reject all

frequency command values between 30.0 and 36.0 Hz.

A frequency command in the deadband will be converted to the bottom
value of the deadband, e.g. a command of 33 Hz would result in a run
frequency of 30 Hz.

FREQ. CMD

36 Hz
33 Hz
30 Hz

0

Total Deadband = 6.0 Hz

± Cn-19 (3.0 Hz)

OUTPUT FREQUENCY (Hz)

2-8