2.11 ENERGY SAVING OPERATION

bn-09: Energy Saving Gain

Factory setting:

80

%

Range: 0 to 200 %

This constant sets, in increments of 1%, the level to which the output voltage is reduced
during the energy-saving operation.

Output Voltage During Energy-Saving Operation

Sn-15 thru Sn-18: Multi-function

Data

63

: Energy Saving Operation

Inputs (Term. 5 thru 8)

A multi-function input may be utilized to
command energy saving operation.

When the external Energy-Saving Operation
command is closed at set frequency, the energy-
saving operation shown below is enabled. In the
energy saving operation, the output voltage is
the value of the energy saving gain (bn-09;
factory set at 80%) multiplied by the V constants
defined by Cn-03, -06 and -08.

NOTE

If energy saving operation is enabled before accel
time is complete, output V/Hz is not affected until
set frequency is reached; then output voltage is
reduced by energy-saving gain (bn-09) setting.

Energy-Saving Run Timing

V/f
CONVERSION

TORQUE
COMPENSATION

VOLTAGE COMMAND

ENERGY-
SAVING GAIN

CLOSE AT SET

FREQUENCY AND

ENERGY-SAVING ENABLED

O O

O

EXTERNAL

CONTACTS

GPD 503

5 Sn-15

6 Sn-16 MULTI-

> FUNCTION

7 Sn-17 INPUT

8 Sn-18

11

0V

RUN COMMAND

ENERGY-SAVING COMMAND

V (of Cn-03, -06 & -08) x

OUTPUT VOLTAGE

ENERGY-SAVING GAIN (bn-09)

2-14