Section 6. FAILURE INDICATION AND DETAILS

6.1 GENERAL

A failure in the GPD 503 can fall into one of two categories.

A blinking "Alarm" indication is a warning that a GPD 503 trouble condition will soon
occur, or that a problem exists in the external circuitry. The GPD 503 will continue to
operate during an "Alarm" indication. "Alarm" indications are not entered into the fault
register.

A steady "Fault" indication is displayed when the GPD 503’s Fault relay has tripped
(GPD 503 shutdown). The motor coasts to a stop, and a fault signal output is present at
control circuit terminals 18 - 20.

INDICATION

(DISPLAY)

FAILURE INDICATION ITEM

DESCRIPTION

bb

External Base Block

Base Block command at multi-function terminal is active,

(blinking)

command

shutting off GPD 503 output (motor coasting). Temporary
condition, cleared when input command is removed.

bUS

Transmission error

Control data cannot be received normally for
longer than 2 seconds.

CALL

Communication ready

Drive is waiting for the PLC to establish communication.

CPF00

Transmission error or control

Transmission between GPD 503 and remote operator is

function hardware fault

not established within 5 seconds after the power supply is

(including internal RAM,

turned on. (Displayed on the remote operator.)

external RAM or PROM)

CPF01

Transmission error

Transmission error occurs 2 seconds or more
after transmission has first been established.

CPF02

Base block circuit failure

GPD 503 failure.

CPF03

NV-RAM (S-RAM) fault

GPD 503 failure.

CPF04

NV-RAM (BCC, Access Code)

GPD 503 failure. This fault may be caused after changing

fault

EPROM chips. Perform a Sn-03 Reset operation to
attempt to clear this fault.

CPF05

A/D converter failure in CPU

GPD 503 failure.

CPF06

Optional connection failure

Improper installation or wiring of option card.

CPF20

A/D converter failure

Defective option card.

CPF21

Transmission interface card

Defective option card. Check option card connector for

(option) self-analysis

proper installation.

function fault

CPF22

Model code fault

Defective option card. Check option card connector for
proper installation.

CPF23

Mutual-analysis function

Defective option card. Check option card connector for

fault

proper installation.

Table 6-1. Failure Indication and Details

INDICATION

(DISPLAY) FAULT

DESCRIPTION

6-1

Advertising