2.20 MULTI-FUNCTION ANALOG MONITOR OUTPUT (Term. 21 & 22)

Sn-05: Operation Mode Select 2

Digit 4 [ X X X X ] : Multi-function

Analog Output

Factory setting: 0 X X X

Sn-09: Analog Monitor Selection

Digit 2 [ X X X X ] : Multi-function

Analog Output

Factory setting: X X 0 X

The monitor output provides a 0-10 Vdc signal
proportional to either output frequency, output
current, output voltage reference, or output power
between terminals 21 & 22:

Sn-05

Sn-09

0 X X X

X X 0 X = 0-10 Vdc proportional

to output frequency

1 X X X

X X 0 X = 0-10 Vdc proportional

to output current

0 X X X

X X 1 X = 0-10 Vdc proportional

to output voltage reference

1 X X X

X X 1 X = 0-10 Vdc proportional

to output power.

bn-11: Analog Monitor Channel 1 Gain

Factory Setting:

1.00

Range: 0.01 to 2.55

This constant is used to calibrate, in increments of 0.01, either the frequency or current
meter connected to terminals 21 & 22. This function is also used to calibrate Channel 1 of
one of the analog output options.

NOTE: When an analog output option is connected, bn-11 setting affects
both terminals 21 & 22 and the option terminals for Channel 1.

2-29

GPD 503

21

Analog

output 22

(0-10 Vdc)

MULTI-
FUNCTION
MONITOR
OUTPUT

+ –

FREQUENCY / CURRENT

METER

(1mA FULL SCALE)