Yaskawa GPD503 Drive User Manual

Page 122

Advertising
background image

TROUBLESHOOTING CHART 7.8

INVERTER OVERHEATED (

oH

) FAULT INDICATION

IS AMBIENT

TEMPERATURE

45°C (113°F)

OR GREATER?

REDUCE AMBIENT
TEMPERATURE.

HEAT SINK
THERMOSWITCH
IS FAULTY.

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

IS HEAT SINK

CLEAN?

COOLING FAN

STOPPED?

CLEAN HEAT
SINK.

REPLACE
COOLING FAN.

WITH POWER OFF, DISCON-

NECT HARNESS CONNECTOR

FROM 17CN ON CONTROL PCB.

USE OHMMETER (X1 RANGE)

TO MEASURE BETWEEN PINS

6 AND 7. DOES METER INDI-

CATE A SHORT AFTER GPD 503

HAS HAD SUFFICIENT

TIME TO COOL?

RECONNECT HARNESS

CONNECTOR TO 17CN.

ERRONEOUS OPERATION

DUE TO NOISE?

CONTROL PCB OR BASE
DRIVE PCB IS FAULTY.
REPLACE FAULTY BOARD.

REMOVE NOISE SOURCE:

• CONNECT SURGE
SUPPRESSOR TO RELAY
AND MAGNETIC CON-
TACTOR COILS.

• PROVIDE LINE FILTER
TO REMOVE NOISE ON
INPUT POWER LINE.

7-10

Advertising