2.24 REMOTE/LOCAL AND REFERENCE SELECTION Continued

Mode 4 uses An-01 thru An-08 and Analog Manual.

The input commands at terminals 5 thru 8 are
binary coded to select the appropriate reference
command, where An-01 is selected by binary zero
and Analog Manual is selected by binary 8. For
example, if the value in An-04 is the desired
frequency reference, enter 0011 at terminals 5
thru 8. As a standard, the right-most bit and
terminal 5 are the LSB.

Sn-04 = remote operation.
Sn-15 = frequency reference select 1 at

terminal 5 (Auto/Manual).

Sn-16 = frequency reference select 2 at

terminal 6.

Sn 17 = frequency reference select 3 at

terminal 7.

Sn-18 = the multi-function analog input

reference select at terminal 8.

Sn-19 = manual reference at terminal 16.

2-WIRE CONTROL

3-WIRE CONTROL

Sn-04 = X X X

0

Sn-04 = X X X

0

Sn-15 =

03

Sn-15 =

00

Sn-16 =

04

Sn-16 =

03

Sn-17 =

05

Sn-17 =

04

Sn-18 =

0C

Sn-18 =

0C

Sn-19 =

00

*

Sn-19 =

00

*

* Sn-19 selects the function of the multi-function analog input. If data value

00

is

entered, the analog input represents manual reference. If An-02 is to be utilized,
then Sn-19 MUST NOT be set to

00

.

GPD 503

5 (Sn-15)

6 (Sn-16)

7 (Sn-17)

8 (Sn-18)

F000.0

Freq.

External Terminal

Ref.

8

7

6

5

An-01

0

0

0

An-02 *

0

0

1

An-03

0

1

0

An-04

0

1

1

Analog -

1

X

X

Manual

Freq.

External Terminal

Ref.

8

7

6

5

Freq.

External Terminal

Ref.

8

7

6

5

An-01

0

0

0

0

An-02 *

0

0

0

1

An-03

0

0

1

0

An-04

0

0

1

1

An-05

0

1

0

0

An-06

0

1

0

1

An-07

0

1

1

0

An-08

0

1

1

1

Analog -

1

X

X

X

Manual

Freq.

External Terminal

Ref.

8

7

6

5

1 = Closed; 0 = Open;
X = No effect;

= FWD/REV

2-38