2.33 V/f PATTERN - CUSTOM Continued

Initial Voltage Values *

When Sn-02 = 01 When Sn-02 = 0F

B.

Cn-02: Frequency – Max. (Fmax)
Cn-03: Voltage – Max. (Vmax)

. . . . . . . . . . . . .

230.0

V

200.0

V

Cn-04: Frequency – Max. Voltage point (F

A

)

Cn-05: Frequency – Midpoint (F

B

)

Cn-06: Voltage – Midpoint (V

C

)

. . . . . . . . . . . . .

17.2

V

15.0

V

Cn-07: Frequency – Min. (Fmin)
Cn-08: Voltage – Min. (Vmin)

. . . . . . . . . . . . .

11.5

V

10.0

V

* Double indicated values for 460V units;

2.5 times indicated values for 575V units.

These seven control constants define the custom V/f pattern, only if Sn-02 is set to

0F

.

The illustration below shows how these constants relate to each other in establishing the
custom V/f pattern.

2-49

NOTE: To establish a V/f pattern with a straight line from Fmin to F

A

, set

F

B

= Fmin. The setting of V

C

is then disregarded and does not affect the

V/f pattern.

IMPORTANT

The constant settings are checked whenever power is applied to
the GPD 503, or each time the DATA/ENTER key is pressed while in
the Program (PRGM) mode. A constant set value failure (

oPE

) will

occur if any part of the following relationships among Cn-02 thru
Cn-08 is not TRUE:

(a)

Fmax

* F

A

* F

B

* Fmin

(b)

Vmax > V

C

* Vmin

V/f Characteristics Set by Cn-02 thru Cn-08

Vmax

(03)

OUTPUT

VOLTAGE

V

C

(06)

Vmin

(08)

Fmin

F

B

F

A

Fmax

(07)

(05)

(04)

(02)

OUTPUT FREQUENCY

[ Parenthesized values indicate control constant numbers. ]