A1-4 – Yaskawa GPD503 Drive User Manual

Page 128

Advertising
background image

CONSTANT

SET

FACTORY

USER

PARA.

NUMBER

DATA NAME

DIGIT

DATA

FUNCTION

SETTING

SETTING

REF.

Sn-06 Operation Mode

XXXX

00 = S-curve at Accel/Decel,

0000

2.27

Select 3

with 0.2 second delay

01 = S-curve at Accel/Decel

disabled

10 = S-curve at Accel/Decel,

with 0.5 second delay

11 = S-curve at Accel/Decel,

with 1.0 second delay

XXXX

0

Output frequency propor-

2.3

tional to Auto reference

1

Output frequency inversely
proportional to Auto ref.

XXXX

0

Auto Reference - Loss

2.4

Detection disabled

1

Auto Reference - Loss
Detection enabled

Sn-07 Overtorque

XXXX

0

Overtorque detection is

0000

2.22

Detection

disabled

1

Overtorque detection is
enabled

XXXX

0

Detects only during set
frequency

1

Detects during all
frequency conditions

XXXX

0

Operation continues after
overtorque detection

1

Coasts to stop when over-
torque is detected

XXXX

– Not

Used

Sn-08 Option Ref-

XXXX

0

Operated from installed

0100

See

erence Select

option

Option

1

Operated from Digital

Instructions

Operator and/or
external terminals

XXXX

0

Run/Stop from installed
option card

1

Run/Stop from Digital
Operator and/or
external terminals

Table A1-3. System Constants (Sn-XX) - Continued

CONSTANT

SET

FACTORY USER

PARA.

NUMBER DATA NAME DIGIT DATA

FUNCTION

SETTING SETTING

REF.

A1-4