2.19 MULTI-FUNCTION INPUT TERMINALS (Term. 5-8) Continued

DESCRIPTION

DATA

FUNCTION

Signal Levels: 0 = state; 1 = pulse

00

FWD/REV selection (for

MUST BE SET IN Sn-15. Redefines terminals:

3-wire control)

1 = Run; 2 = Stop;
5 = FWD/REV select

01

Operation signal selection

Open 0 = Operates according to setting of

(Remote/Local)

Sn-04, digits 1 & 2 [ X X

0 0

]

Closed 0 = Operates from keys of the

Digital Operator

See Data description following this table

02

Option/GPD 503 reference

Open 0

= Operates from installed option

selection

Closed 0 = Operates from Digital Operator and/or

external terminals

03

Multi-step speed ref. 1

04

Multi-step speed ref. 2

See paragraph 2.24

05

Multi-step speed ref. 3

06

JOG1 selection

Closed 0 = Jog selected See paragraph 2.15

07

Accel/decel time

Open 0 = Accel/decel by bn-01/bn-02
Closed 0 = Accel/decel by bn-03/bn-04
See paragraph 2.2

08

External base block

Closed 0 = Shuts off GPD 503 output

(N.O. contact input)

(frequency command is held)

See Data description following this table

09

External base block

Open 0 = Shuts off GPD 503 output

(N.C. contact input)

(frequency reference is held)

See Data description following this table

0A

Accel/decel speed prohibit

See Data description following this table

(HOLD command)

0b

External overheat

Closed 0 =

oH2

blinks on the Digital Operator, and

operation continues (minor fault)

0C

Multi-function analog input

Closed 0 = Analog input (term. 16) is enabled

selection

Open 0 = Analog input (term. 16) is disabled

0D

to

0F

Not Used

10

UP function

See paragraph 2.34

11

DOWN function

12

JOG2 - FWD

See paragraph 2.15

13

JOG2 - REV

DESCRIPTION

DATA

FUNCTION

Signal Levels: 0 = maintained; 1 = momentary

2-25

Table 2-2. Sn-15 thru Sn-18 Data Settings