2.2 ACCEL/DECEL TIME

A. bn-01: Accel Time 1

Factory setting (each):

10.0

seconds

bn-02: Decel Time 1

Range (each): 0.0 to 6000.0 seconds

bn-03: Accel Time 2

bn-04: Decel Time 2

The GPD 503 incorporates two sets of individually programmable acceleration and
deceleration times.

B. Sn-15 thru Sn-18: Multi-

Data

07

: Accel/Decel Time Selection

function Inputs (Term. 5 thru 8)

By programming data 07 into one of the multi-
function system constants (Sn-15 thru Sn-18),
one of the multi-function input terminals (5 thru
8) becomes a time selection input. When the
input terminal (i.e. external contact) is open,
Time 1 (bn-01/bn-02) is selected. When the
input terminal is closed, Time 2 (bn-03/bn-04)
is selected.

C. Sn-19: Multi-function Analog

Data

06

: Accel/Decel Time Coefficient

Input (Term. 16)

The multi-function analog input at terminal 16
may be configured to allow analog control of the
Accel/Decel time. The input voltage, in the
range of 1 to 10V, determines the coefficient by
which the Accel/Decel time is reduced:

Actual Accel/ = Accel/Decel Time

Decel Time

Coefficient

EXAMPLE:

Accel/Decel Time = 10 sec *
Voltage Ref. at Term. 16 = 5V

Actual Accel/ =

10 sec = 2 sec

Decel Time

5 (coefficient)

* bn-01 or bn-03 setting

TIME 1 o

o

o

TIME 2

GPD 503

7

11

0V

ACCEL/
DECEL
COEFFICIENT

1R

GPD 503

15 +15V

16 0-10V (20K

1

)

17

C

10

5

COEFFICIENT

1

0

1

5

10

VOLTAGE

2-3