2.8 DC INJECTION BRAKING

A. Sn-04: Operation Mode Select 1

Digits 3 & 4 [ X X X X ] : Motor

Stopping Method Selection

Factory setting:

0 0

X X

Cn-12: DC Injection Time at Stop

Factory setting:

0.0

sec

Range: 0.0 - 25.5 sec

When full range DC injection braking stop is enabled (Sn-04 =

1 0

X X), DC injection

braking is used to stop a motor more quickly than normal coast to stop, without the need
for braking resistors. When a STOP command is issued, there is a 0.5 second time delay
to apply DC to two phases of the motor’s stator winding. Then DC injection current is
applied. The duration of DC braking is a time period proportional to Cn-12 (at 10% output
frequency) and the level of output frequency at the time the STOP command is issued.

Braking torque is 50-70% of full load motor torque.

EXAMPLE:

Cn-12 = 0.5 sec (at 10% output)

Braking time at Fmax (100% output frequency) = 10 x 0.5 = 5 sec

Full Range DC Injection Braking Stop Sequence

RUN CMD

OUTPUT

FREQUENCY

STOP

0.5 sec

COASTING

DC BRAKING TIME

Cn-12 x 10

DC IN-
JECTION
BRAKING
TIME

Cn-12

0 10%

100%

OUTPUT FREQUENCY

AT TIME OF STOP COMMAND