TROUBLESHOOTING CHART 7.1

MOTOR WILL NOT RUN

"CHARGE" LAMP

ON MAIN PC BOARD

LIT?

CHECK CIRCUIT
BREAKER, MAGNETIC
CONTACTOR AND
INPUT POWER.

NO

NO

NO

NO

NO

(CONTROL BY EXT. INPUTS)

NO

(CONTROL

BY DIGITAL

OPERATOR)

NO

NO

YES

YES

YES

YES

YES

YES

YES

RATED VOLTAGE

ACROSS TERMINALS

L1 (R), L2 (S), AND L3 (T)?

FAULT CODE

SHOWN ON

ALPHA-NUMERIC

DISPLAY?

GO TO
APPROPRIATE
CHART, 7.3 THRU
7.10

RUN

LAMP

ON?

STOP COMMAND

STILL ON?

(CLOSED CIRCUIT

BETWEEN TERMINALS

11 AND 2)

RUN

COMMAND ON?

(CLOSED CIRCUIT

BETWEEN TERMINALS

11 AND 1)

RELEASE STOP
COMMAND INPUT.

INPUT RUN
COMMAND.

GPD 503'S
CONTROL POWER
CIRCUIT IS
FAULTY.

APPROX. 15VDC FROM

TERMINAL 15(+) TO 17?

A

TO NEXT
PAGE

DIGITAL

OPERATOR

ASSEMBLY

IS FAULTY.

REPLACE.