Run operative settings (bn-xx), A1-2, Table a1-2. run operative settings (bn-xx) – Yaskawa GPD503 Drive User Manual
Page 126
CONSTANT
INCRE- SETTING
FACTORY
USER
PARA.
NUMBER
DATA NAME
MENT
RANGE
SETTING SETTING
REF.
bn-01 Accel Time 1
0.1 s 0.0 - 6000.0
10.0
2.2A, 2.2C,
2.18
bn-02 Decel Time 1
0.1 s 0.0 - 6000.0
10.0
2.2A, 2.2C,
2.18
bn-03 Accel Time 2
0.1 s 0.0 - 6000.0
10.0
2.2A, 2.2C,
2.18
bn-04 Decel Time 2 ( also Emergency
0.1 s 0.0 - 6000.0
10.0
2.2A, 2.2C,
Stop Decel Time )
2.18
bn-05 Frequency Command Gain
0.1 % 0 - 1000.0
100.0
2.13
bn-06 Frequency Command Bias
1 % –100 to 100
0
2.13
bn-07 Torque Compensation Gain
0.1 0.0 - 2.0
1.0
2.31
bn-08 Slip Compensation Gain
0.1 % 0.0 - 9.9
0.0
2.26,
(Motor Rated Slip)
2.35
bn-09 Energy Saving Gain
1 % 0 - 200
80
2.11
bn-10 Monitor No. After Power-up
1
1 - 3
1
2.10
bn-11 Analog Monitor Channel
0.01
0.01 - 2.55
1.00
2.20 (1)
1 Gain
bn-12 Analog Monitor Channel
0.01
0.01 - 2.55
0.50
(1)
2 Gain
(1) Refer to separate Option Instruction Sheet.
CONSTANT
INCRE-
SETTING FACTORY USER PARA.
NUMBER
DATA NAME
MENT RANGE
SETTING SETTING
REF.
CONSTANT
INCRE-
SETTING FACTORY USER
PARA.
NUMBER
DATA NAME
MENT RANGE SETTING SETTING
REF.
Table A1-2. Run Operative Settings (bn-XX)
A1-2