A1-9 – Yaskawa GPD503 Drive User Manual

Page 133

Advertising
background image

CONSTANT

SET

FACTORY

USER

PARA.

NUMBER

DATA NAME

DIGIT

DATA

FUNCTION

SETTING

SETTING

REF.

Sn-26

Digital Speed

XXXX

0000 = BCD input, 1% accuracy

0000

Separate

Reference

0001 = BCD input, 0.1% accuracy

Option

(DI-08)

0010 = BCD input, 0.01% accuracy

Instruction

Frequency

0011 = BCD input, 1Hz

Sheet

reference

0100 = BCD input, 0.1Hz

set mode

0101 = BCD input, 0.01Hz

selection

0110 = Reserve

0111 = Binary input, 255 / 100%
1000 = Binary input (set value

displayed in decimal on
Digital Operator)

Sn-27

Digital Output XXXX

0

DO-08 output signal

0010

Separate

Card (DO-08)

combination 1 (output

Option

data fixed)

Instruction
Sheet

1

DO-08 output signal
combination 2 (encoded
output)

Pulse Monitor

XXXX

Number of

000 = 1F

Separate

(PO-36F)

output

001 = 6F

Option

pulses

010 = 10F

Instruction

selection

011 = 12F

Sheet

100 = 36F

Sn-28

Analog Monitor XXXX

Select item to

00 = Output

0100

Separate

(AO-08 or

output from

frequency (max.

Option

AO-12)

channel 1

frequency /100%)

Instruction

01 = Output current

Sheet

(rated current

XXXX

Select item to

/100%)

output from

10 = Output voltage

channel 2

ref. (input
voltage /100%)

11 = DC voltage [Vpn]

(400V /100%)

[230V drives]

(800V /100%)

[460V drives]

(1000V /100%)

[575V drives]

Table A1-3. System Constants (Sn-XX) - Continued

CONSTANT

SET

FACTORY USER

PARA.

NUMBER DATA NAME DIGIT DATA

FUNCTION

SETTING SETTING

REF.

A1-9