A2-3 – Yaskawa GPD503 Drive User Manual

Page 141

Advertising
background image

SECTION C. ALL GPD 503 s (CONTINUED)

Control

Braking Torque

Approximately 20%

Characteristics
(continued)

V/F Pattern Selection

15 Standard Patterns:

4 for general purpose;

4 for high starting torque;

4 for fans and pumps;

3 for machine tools.

1 custom pattern: defined by control constant settings.

Motor Overload Protection

Electronic thermal overload relay

Instantaneous Overcurrent

Motor coasts to a stop at approximately 200% rated current.

Fuse Blown Protection

Motor coasts to a stop by blown fuse.

Overload

Motor coasts a stop after 60 sec. overload condition.

Overvoltage

Motor coasts to a stop if GPD 503 DC bus voltage exceeds
400 V (230V unit), 800V (460V unit), 1040V (575V unit).

Protective

Undervoltage

Motor coasts to a stop if GPD 503 DC bus voltage drops to

Functions

210 V or below (230V unit), 420V or below (460V unit),
546V or below (575V unit).

Momentary Power Failure

Factory setting provides for motor to coast to a stop after
momentary power failure of more than 15 ms. Can be
reprogrammed to allow continuous operation (ride-through)
during power failure of up to 2 seconds (see Note 4).

Heatsink Overheat

Thermostat

Stall Prevention

Stall prevention at acceleration /deceleration and constant
speed operation.

Ground Fault

Provided by electronic circuit.

Power Charge Indication

"CHARGE" lamp remains lit until bus voltage drops below 50 V.

Location

Indoor (protected from corrosive gases and dust).

Ambient Temperature

-10 to 40oC (+14 to 104°F)

Environmental
Conditions

Storage Temperature (Note 5)

-20 to 60oC (-4 to 140°F)

Humidity

90% RH (no condensation)

Vibration

1 G at less than 20 Hz, up to 0.2 G at 20 to 50 Hz.

SECTION B. ALL GPD 503 s (Continued)

NOTES:

1.

Overload capacity: 150% of rated for 60 sec.

2.

Overload capacity: 125% of rated for 60 sec.

3.

Overload capacity: 115% of rated for 60 sec.

4.

For a 230/460 V GPD 503 less than 5HP, ride-through function up to 2 second momentary power failure requires
connection of an external capacitor unit between external main circuit terminals B1/+ and –.

5.

Temperature during shipping. Storing in this temperature for a long period may deteriorate main circuit capacitor.

Table A2-1. Standard Specifications (Continued)

A2-3