2.5 AUTO-RESTART

A. Cn-36: Number of Auto-Restart Attempts

Factory setting:

00

Range: 00 - 10

When a fault occurs during operation, the GPD 503 can be programmed for an auto-
restart operation to automatically reset the fault. Auto-restart operation will use the
number of reset attempts set in this constant, up to the maximum of 10. When set to

00

,

no auto-restarts will be attempted.

• The following faults can be automatically reset:

oC:

Overcurrent

oL3:

Overtorque

ou:

Overvoltage (OV)

oH:

Overheat

oL2:

Inverter overload

Uu1: Undervoltage (Power UV)

• The following conditions WILL NOT initiate auto-restart:

1. oL1, EF , FU or CPF

fault.

2. When OC or UV occurs during deceleration.
3. When Sn-11, digit 3 ( X 0 X X ) is programmed to stop during momentary power

failure. (See para. 2.16, MOMENTARY POWER LOSS RIDE-THRU.)

• The number of restart attempts available will be reset to the Cn-36 setting when:

1. 10 minutes has elapsed without a fault occurring.
2. The RESET key, or external Fault Reset push button, is pressed.

B. Sn-11: Protective Characteristics

Digit 2 [ X X X X ]: Fault Contact

Select 2

Status During Auto-Restart

This digit controls how the fault contact responds to a GPD 503 fault during the auto-
restart operation.

0: Fault contact will not actuate during auto-restart attempts

1: Fault contact actuates during auto-restart attempts

Auto-Restart Operation Timing

2.6

Intentionally Deleted

FAULT DETECTION

FAULT CONTACT

OUTPUT FREQUENCY

Sn-11 = X X 1 X
Sn-11 = X X 0 X

MOTOR RPM

100 ms

AUTOMATIC FAULT RESET

Time from fault detection

to reset attempt, or time

between reset attempts