Yaskawa GPD503 Drive User Manual

Page 109

Advertising
background image

INDICATION

(DISPLAY)

FAILURE INDICATION ITEM

DESCRIPTION

EF

Simultaneous forward and

Fwd Run and Rev Run commands are both closed for

(blinking)

reverse operation commands

more than 500 ms. Removing one command will allow
drive operation.

EF0

External fault

GPD 503 is in Stop mode.

EF3

Ext. fault signal at term. 3

A fault condition has occurred in the external circuit(s)

EF5

Ext. fault signal at term. 5

monitored by the contact providing input to the indicated

EF6

Ext. fault signal at term. 6

terminal.
If display is steady, GPD 503 is in Stop mode; if display

EF7

Ext. fault signal at term. 7

is blinking, the terminal is programmed to allow continued

EF8

Ext. fault signal at term. 8

operation after receiving fault input.

E r r

Constant write-in fault

Temporary display, in Program mode, indicating that
constant setting was not written into EPROM memory.

FAn

Cooling fan failure

GPD 503 is in Stop mode.

FU

Fuse blown

DC Bus fuse has cleared. Check for short circuit
in output, and check main circuit transistors.

GF

Ground fault protection

Ground current > approx. 50% of the GPD 503 rated
current.

oC

Overcurrent

GPD 503 output current exceeds 200% of GPD 503
rated current, or ground fault has occurred, with ground
current exceeding 50% of GPD 503 rated current.

oH

Heat sink overheated

Fin temperature exceeds 90° C (194° F)

oH2

External overheat

External temperature monitoring circuit(s) detected an

(blinking)

overtemperature condition and produced an input signal.

oL1

Overload

Thermal motor overload protection has tripped.

oL2

Overload

GPD 503 overload protection has tripped.

oL3

Overload

GPD 503 output torque exceeds the set Overtorque

(blinking)

Detection level, but GPD 503 is programmed for
continued operation at overtorque detection.

oL3

Overload

GPD 503 output torque exceeds the set Overtorque
Detection level, and GPD 503 is programmed for
coast to stop at overtorque detection.

oPE01 *

kVA constant setting fault

Sn-01 setting is incorrect.

oPE02 *

Constant setting range fault

An-XX, bn-XX, Cn-XX, or Sn-XX setting range fault.

oPE03 *

Constant set value fault

Sn-15 to -18 (multi-function input) set value fault.

oPE04 *

Constant set value fault

PG constant, number of poles, or PG division rate set
incorrectly.

oPE10 *

Constant set value fault

Cn-02 to -08 (V/f data) set incorrectly.

oPE11 *

Constant set value fault

One of the following conditions was detected:

• Cn-23 > 5 KHz and Cn-24

5 KHz

• Cn-25 > 6 and Cn-24 > Cn-23

* These fault displays occur only when in the Program mode, when changing back to

Drive mode from Program mode, or when applying power to the GPD 503.

Table 6-1. Failure Indication and Details - Continued

INDICATION

(DISPLAY) FAULT

DESCRIPTION

6-2