Appendix 3. gpd 503 capacity, A3-1 – Yaskawa GPD503 Drive User Manual

Page 142

Advertising
background image

Appendix 3. GPD 503 CAPACITY

System Constant Sn-01 (GPD 503 Capacity) is factory preset per the voltage and horse-
power ratings of the GPD 503. Table A3-1 identifies the set value, per Model Number. If
the Control PCB is replaced, the new board MUST have Sn-01 programmed to the
appropriate set value BEFORE again operating the GPD 503 in the Drive mode.

HP

Motor Rated Current

Reference Current For

Sn-01

Rating

Max Motor Output Current (Amps) (Cn-09)

Setting Constants (Amps)

Set Value (CT)

HP - (KW)

(See Note 1)

(See Note 2)

2 3 0 V

01

DS305 1

(0.75)

3.3

4.8

02

DS302 2

(1.5)

6.1

6.4

03

DS306 3

(2.2)

8.5

9.6

04

DS307 5

(3.7)

14.1

16

05

DS308 7.5

(5.5)

20.7

24

06

DS309 10

(7.5)

27.5

32

07

DS310 15

(11)

39.7

48

08

DS311 20

(15)

53.0

64

09

DS322 25

(18.5)

65.8

80

0A

DS323 30

(22)

77.2

96

0b

DS2040

40

(30)

105

130

0b GPD503-2L40

40/50

(30)

105

130

0C

DS2050

50

(37)

131

160

0C GPD503-2L50

60

(37)

131

160

0d

DS2060

60

(45)

156

183

0d GPD503-2L60

60

(45)

156

183

0E

DS2075

75

(55)

190

224

0E GPD503-2L75

75

(55)

190

224

0F

DS2100

100

(75)

240

300

0F GPD503-2L100

100

(75)

240

300

4 6 0 V

21

DS313

1

(0.75)

1.7

2.6

22

DS304

2

(1.5)

3.1

4.0

23

DS314

3

(2.2)

4.2

4.8

24

DS315

5

(3.7)

6.8

8.0

25

DS316

7.5

(5.5)

10.2

12

26

DS317

10

(7.5)

13.4

16

27

DS318

15

(11)

20.1

24

28

DS326

20

(15)

26.7

32

29

DS325

25

(18.5)

33.4

40

2A

DS330

30

(22)

38.5

48

2b

DS340

40

(30)

52.5

64

See NOTES on next page.

Table A3-1. GPD 503 Capacity

Drive

Motor Rated Current GPD 503 Rated Current

Sn-01 Model Max Motor Output

(Amps) (Cn-09)

(Amps) (

Reference Current For

Set Value No.

HP - (kW)

(See Note 1)

Setting Constants;

See Note 2)

A3-1

( "L" ) (04/27/95)

Advertising