Yaskawa GPD503 Drive User Manual

Page 56

Advertising
background image

Sn-19 = 00

100%

FREQUENCY

REF.

0%

0V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 01

2.00

FGAINE

1.00

0V

5V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 02

10%

FBIAS1

0%

0V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 03

10%

FBIAS2

0%

- 10%

0V

5V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 04

OVER-

200%

TORQUE
DETECTION
LEVEL

0%

0V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 05

100V

VBIAS

0V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 06

10

REDUCTION
COEFFI-
CIENT

1

0V

1V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 07

100%

DC IN-
JECTION
BRAKING
CURRENT

0%

0V

10V

MULTI-FUNCTION ANALOG INPUT

Actual Accel or decel time = Accel or decel time

Coefficient

2-23

2.18 MULTI-FUNCTION ANALOG INPUT (Term. 16) Continued

Sn-19 = 08

STALL

200%

LEVEL
DURING

100%

RUNNING

( PERCENT OF

30%

Cn-30 SETTING)

0

1.5V

5V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 09

MAX. OUTPUT FREQUENCY

(Cn-02)

FREQUENCY
REFERENCE
LOWER
LIMIT

0V

10V

MULTI-FUNCTION ANALOG INPUT

Sn-19 = 0A

MAX. OUTPUT FREQUENCY

(Cn-02)

SETTING
PROHIBITED
FREQUENCY 4

0V

10V

MULTI-FUNCTION ANALOG INPUT

Advertising