2.9 DIGITAL DISPLAY SELECTION
Cn-20: Operator Display Mode
Factory setting:
0
Reference and Indication
Range: 0 to 39999
This constant designates what Drive parameter will be displayed on the Digital Operator
when the GPD 503 is in the Drive mode. It will be displayed where "OUTPUT
FREQUENCY" was previously displayed.
DATA
PARAMETER DISPLAY
0
Output frequency, in increments of
(factory 0.1
Hz.
setting)
1
Same as
0
2
to
39
Motor synchronous speed (N
S
=
(no. of motor
in increments of 1 RPM
poles)
(39999 max).
NOTE: When motor synchronous
speed exceeds 39999 RPM,
display holds at
3 9 9 9 9
.
0 0 0 4 0
Line speed or other parameter. Setting
to
must be 5 digits.
3 9 9 9 9
X X X X X
Parameter value at maxi-
mum frequency (include
leading zeroes if necessary)
Location of decimal point:
0
= X X X X
1
= X X X . X
2
= X X . X X
3
= X . X X X
(See
CAUTION
on next page)
EXAMPLE:
To display Line Speed, based on
54.32 FPM at 60 Hz:
Cn-20 setting =
2 5 4 3 2
DATA
PARAMETER DISPLAY
2-12
120F
)