9 digital display selection – Yaskawa GPD503 Drive User Manual

Page 43

Advertising
background image

2.9 DIGITAL DISPLAY SELECTION

Cn-20: Operator Display Mode

Factory setting:

0

Reference and Indication

Range: 0 to 39999

This constant designates what Drive parameter will be displayed on the Digital Operator
when the GPD 503 is in the Drive mode. It will be displayed where "OUTPUT
FREQUENCY" was previously displayed.

DATA

PARAMETER DISPLAY

0

Output frequency, in increments of

(factory 0.1

Hz.

setting)

1

Same as

0

2

to

39

Motor synchronous speed (N

S

=

(no. of motor

in increments of 1 RPM

poles)

(39999 max).

NOTE: When motor synchronous

speed exceeds 39999 RPM,
display holds at

3 9 9 9 9

.

0 0 0 4 0

Line speed or other parameter. Setting

to

must be 5 digits.

3 9 9 9 9

X X X X X

Parameter value at maxi-
mum frequency (include
leading zeroes if necessary)

Location of decimal point:

0

= X X X X

1

= X X X . X

2

= X X . X X

3

= X . X X X

(See

CAUTION

on next page)

EXAMPLE:

To display Line Speed, based on
54.32 FPM at 60 Hz:

Cn-20 setting =

2 5 4 3 2

DATA

PARAMETER DISPLAY

2-12

120F

)

P

Advertising