17 monitor display (digital operator) – Yaskawa GPD503 Drive User Manual
Page 54
2.17 MONITOR DISPLAY (DIGITAL OPERATOR)
While in the Drive mode, different information will appear on the Digital Operator display
when each of the Un constants is selected (see page 3-7).
CONSTANT
DISPLAY
Un-
MONITORED ITEM
EXAMPLE
01
Frequency reference
60.0
02
Output frequency
60.0
03
Output current
12.5A
04
AC voltage reference
230 v
05
DC Bus voltage ( VPN )
Pn270
06
Output power ( kW )
(±)
12.5
07
Input terminal status
CI I I I
*
08
Output signals status
o I I
**
09
LED lamp check
8.8.8.8.8.
10
Control Section PROM
16142
(last 5 digits of PROM
Part No. :
NSG 6XXXXX
CONSTANT
DISPLAY
Un-
MONITORED ITEM
EXAMPLE
*
Actual display appearance:
**
Actual display appearance:
Term. 5 input OPEN
Term. 6 input CLOSED
Term. 7 input OPEN
Term. 8 input CLOSED
"C" indicates display is Input Terminal Status
"At Speed" output ON
"Zero Speed" output OFF
"Run" status output ON
"o" indicates display is Output Signals Status
Term. 1 input OPEN
Term. 2 input CLOSED
Term. 3 input OPEN
Term. 4 input CLOSED
2-21