Mark-related positioning [posr, 11 mark-related positioning [posr, Operating instructions – Parker Products COMPAX-M /-S (L) User Manual

Page 100: Compax-m / -s, Posr, Mark-related positioning [posr] 100

Advertising
background image

Operating Instructions

COMPAX-M / -S

Mark-related positioning [POSR]

100

8.4.11 Mark-related positioning [POSR]

Use this command to position e.g. a mark relative to an external signal.

POSR value
Value: two digits after the decimal point (three for inches) in unit corresp. to P90; a

control parameter (P40..P49) or a variable (V1..V39)
e.g. POSR .P40.
The prefix determines the direction in which the mark is approached.
Note!
POSR 0 is not permitted!

When the mark reference is activated, do not use the POSA command!

I14:

Activating mark reference .

I14 must be present before the command.

I16:

Mark input

The rising flank is evaluated (pulse > 0.6ms).

(is read in with a rating of 100

µ

s; the max. error is therefore 100

µ

s)

O16:

With "0", the mark is missing after travel to the mark is completed (P38).

P35:

="1": Mark reference switched on;
="0": Mark reference switched off.

P37,P38:

A mark window is specified relative to the start position using P37 and P38.

P37:

Minimum travel to mark. (relative to start position).
Range of values for P37: 0.00 ... P38

P38:

Maximum travel to mark. (relative to start position).
Range of values for P38: P37 ... 4 000 000

P39:

Maximum feed length, if there is no mark in the mark window (relative to start
position).
Range of values for P39: P38 ... P11 or P12

POSR 100

P35="1"; P37=+300; P38=+600; P39=+800; I14="1".

If the mark is between +300 and +600, mark +100 is positioned, if the mark is
outside the window it is positioned to 800.

start point

P37 = +300

P38 = +600

P39 = +800

100

mark on

I16

Driven to

label position

O16

It will go on "0" if no label

come until P38.

Note!
The drive positioning is not limited by P39.
If the mark is within the mark window, COMPAX executes positioning using the
POSR value for a value of the corresponding size, even after P39.
The process range can be limited using P11 and P12.

When the mark reference is switched on, the inputs I14, I15, and I16 are no
longer available for external data record selection (GOTOEXT,
GOSUBEXT).

POSR

Syntax:

Note:

Example:

POSA

POSR

SPEED

ACCEL

OUTPUT

Password

SPEED

SYNC

Mark

reference

POSR

SPEED

POSR

OUTPUT

Cam

controller

WAIT

GOTO

GOSUB

RETURN

END

REPEAT

IF I..

Comparison

WAIT Start

GOTO /

GOSUB EXT

IF Error/ Stop

Arithmetic

Position

monitoring

Idle display

Speed

monitoring

Engage /

disengage

brake / final

stage

Variable

voltage

Advertising