8.4.32 Idle display

Display showing whether the axis is at standstill or moving.
The display is set to output O2 using the setting P227 bit 1

26

="1"

; the standard

function of O2 "No warning" no longer applies in this case.
P229 then serves as a switching threshold, above which an idle condition is
reported with O2="1" and indicated in per-thousands (€ of P104) of nominal speed.

Nominal speed < P229:

O2="1"; drive at standstill

Nominal speed

P229:

O2="0"; drive moving

P229 = 0:

O2="0"; no idle display

Range of numbers P229:

0 - 255‰

P227 bit 1 ="0"

O2 assigned the "No warning" display (default value).

V

P229

O5
Ba1

O2

t

t

t

To avoid O2 continuously switching over during nominal speed value disturbance
(during synchronization applications), a minimum pulse time (

minimum

positioning time) is defined.
Once nominal speed < P229 has been detected and P229 has then been
exceeded again, the next nominal speed check is executed after 50 ms.

V

P229

O2

t

t

50ms

Disturbance

26

Bit counting begins with 0.

Example: