8.5.1 Optimization

parameters

In addition to the standard structure (which corresponds to the previous COMPAX
control structure), you can select from 3 structure variants.
These include, in addition to a specific control structure, pre-defined settings for
specific optimizing parameters. By selecting the individual structures in the
ParameterEditor, the following parameters can be set:

No.

Meaning

Standard

Variant 1

Variant 2

Variant 3

P59

Structure switch measuring

0

4

3

8

P56

D section rpm controller (%)

0

40

40

40

P57

Filter acceleration (%)

100

175

350

100

P58

Lag rapid rpm signal (%)

100

0

0

100

P50

Monitor

100

(switched off)

101

(switched on)

101

(switched on)

100

(switched off)

P151 Monitor speed (%)

30

30

30

30

P27

Moment of inertia (%)

100

100

85

100

P69

Return pre-control (%)

0

100

100

100

P70

Current pre-control value
(%)

0

100

100

100

Standard:

Previous COMPAX control structure; use this structure if you already
have optimized parameter sets.

Variant 1:

Structure switch: Variant 1 for resolver

Variant 2:

Structure switch: Variant 2 for SinCos

Variant 3:

Structure switch: Variant 3 "Rapid rpm controller"

The structure switch measuring (P59) permits the following settings:

No.

Meaning

Settings

Structure switch measuring

0: Standard
4: Variant 1

(for resolver)

3: Variant 2

(for SinCos

)

8: Variant 3

(rapid rpm controller)

Sensitive stiffness (P23)
Larger setting range for P23

+16

P59

Sensitive D section (P56)
Larger setting range for P56

+65536
The D section is reduced by 1/256.

By selecting a structure variant with the structure switch P59, no further
parameters are influenced.
Only by selecting a variant through ServoManager (menu parameters:
controller structure / monitor) can complete parameter sets (as described
above) be set.

The stiffness is proportional to the controller speed.
Nominal value: 100%

Range: 10%...5000%

Control is faster. The control circuit starts from a critical value. Set the stiffness so
that sufficient safety distance from the critical value is ensured.

Control is slower. This increases lag error. Current limitation is reached later.

Structure
variants:

Structure and

parameter settings

using the

ServoManager:

P59: Structure
switch
measuring

P23: stiffness of
drive

Increase stiffness

Reduce stiffness