COMPAX 1000SL Unit characteristics

45

Unit

hardware

Connector

assignment / cable

Technical data

Configuration

Positioning and

control functions

Optimization

functions

Interfaces

Accessories /

options

Status

Parameter

Error list

COMPAX 1000SL X19

Pin

Assignment

23 +24V DC (<50mA)

1

0V

24 P: Ready contact
25 S: Ready contact

25 pin Sub-D
socket strip
screw connection
UNC4-40

14

25

1

13

11 Emergency stop input (activated by 15V – 24V)

Emergency stop input direct to COMPAX-M X9

Pin

Assignment

1

+24V DC (<50mA)

2

0V

3

reserved

4

reserved

5

+24V DC – Output for emergency stop

6

Emergency stop input (activated by 15V – 24V)

Connector: Phoenix
MC1.5/7-ST-3.81

45

67

123

7

Screen

*

Emergency stop input on COMPAX-M

The emergency stop input on COMPAX-M X9 is enabled via parameter P219.
Meaning:

!

P219="0": No emergency stop input on COMPAX-M X9

!

P219="7": Emergency stop input on COMPAX-M X9 with the following data

!

Stop with P10 as relative ramp time (P10 = braking time from 100% speed to
0%).

!

The motor is switched off.

!

Error message E56 is generated.

!

The ready contact drops.

Ready contact:

max. 0.5A,

60V, 30W

control

power supply

module

COMPAX-M

No. 1

COMPAX-M

No. x

external

component

X8/1
X8/2
X8/3
X8/4
X8/5
X8/6

X8/7

+24V
GND

shield

readiness

emerg. stop

X./1
X./2
X./3
X./4
X./5
X./6

X./7

+24V
GND

shield

COMPAX-S X9 i.e. COMPAX 35XXM X19

Applies to potential -
24V power supply.

Principle of safety
chain and
emergency stop
function