7.9.4 Initiators and D/A monitor

Connection assignment on X17

Pin

Assignment

1

DA channel 0 (option D1) Ri=2.8k

;

COMPAX 1000SL:

DA channel 2; Ri=0.33k

;

2

DA channel 1 (option D1) Ri=2.8k

;

COMPAX 1000SL: DA

channel 3; Ri=0.33k

;

3

reserved

4

Ground 24V (Initiators supply)

5

+24V (Initiators supply) <50 mA

6

Ground for DA channels

7

Input MZ initiator

8

Input I2 initiator

9 pin Sub-D pin strip
plug housing with
screw connection
UNC4-40

1

5

6

9

9

Input I1 initiator

X3/9

X3/8

X3/7

X2/6

X2/5

X2/4

X1/3

X1/2

X1/1

X4/15

X4/14

X4/13

X4/12

X4/10

+24V

Sig. MN

GND

initiatorbox

X17/5

X17/9

X17/7

X17/8

X17/4
X17/3

+24V

Sig. E1

Sig. MN

Sig. E2

GND

br

sw

bl

br

ge

gn

ws

bl

E1

E2

4,

75

k

4,

75

k

4,

75

k

+24V

Sig. E2

GND

br

sw

bl

n

orma

lly

close

d pnp

+24V

Sig. E1

GND

br

sw

bl

MN

n

orma

lly

close

d pnp

n

orma

lly

close

d pnp

Ensure that the initiator is rebound-free!

Standard
When operating with one initiator (machine zero), this must be attached to one
side of the stroke. When attaching the initiator, ensure that an initiator attached to
the left-hand side can no longer be cleared to the left. The flank to be analyzed can
therefore also be positioned before the end of the travel distance. The same
applies correspondingly for the right-hand side.
Extended operation
When operating with three initiators (not standard), initiators I1 and I2 must be
attached to the outer limits of the stroke range. The machine zero initiator is fitted
between I1 and I2. The following limitation applies in such cases: the flank of the
machine zero initiator must not be activated at the same time as a limit switch.

If COMPAX is only operating as a speed controller or in the "continuous
mode" or normal operating mode with a special machine zero mode
(P212="10" see Page 80 onwards), then no initiators are required.

Connection plan
for the initiators
with initiator
connector

Requirements

concerning the

position of the

initiators