8.4.3 Process velocity [SPEED]

Process velocity as % of nominal velocity
(Nominal velocity

nominal speed * travel per motor rotation).

valid until a new value is programmed.

When in speed control mode , direction of rotation is specified by the prefix.

SPEED value
Value: 0.0000001...100%

15

, a control parameter (P40..P49) or a variable

(V1..V39) e.g. SPEED .P40

Smallest steps = 0.002384min

-1

N005: SPEED 70 sets velocity to 70% of nominal speed.

The set velocity can be reduced using the analogue overrride input (X11.6)
(see start-up manual).

8.4.4 Acceleration and braking time [ACCEL]

Specification for acceleration and braking time .

without prefix: time specification for acceleration and decceleration process.

negative prefix: separate time specification for decceleration process.

valid until a new value is programmed.

Acceleration process can be specified using parameter P94 (see Page 75).

If a travel command is interrupted by STOP or BREAK, the STOP / BREAK – ramp
is not executed by ACCEL- but by the value defined as the acceleration time.

ACCEL value
Value: 10...65 000 ms, a control parameter (P40..P49) or a variable (V1..V39) e.g.

ACCEL .P40 (timescale = 10 ms)
The negative prefix for the decceleration time specification must be set
before the control parameters e.g.: ACCEL- .P40 (P40 > 0)

The time specified in ms applies for nominal velocity
(100%). The actual time is proportional to the velocity

selected. Meaning:

ACCEL

%

100

SPEED

ta

=

N005: ACCEL 300

sets the acceleration and deceleration ramp to 300 ms

N006: ACCEL -200 sets the deceleration ramp to 200 (

200 ms when

SPEED=100%)

15

For asynchronous motors, up to a max. of 300%.

SPEED

Syntax:

Example:

ACCEL
ACCEL-

Note:

Syntax:

Example:

40%

SPEED
100%

ta

ACCEL