Operating instructions, Compax-m / -s – Parker Products COMPAX-M /-S (L) User Manual

Page 164

Advertising
background image

Operating Instructions

COMPAX-M / -S

RS232 interface

164

Example:

P40 CR LF

COMPAX transmits the contents of P40: P40=value name CR LF>

Instruction

Abbreviated
form

Meaning

START Nxxx

SNxxx

Execute program set xxx (this set only).

START

ST

Start program.

STOP

SP

Stop program/positioning.
SP corresponds to a STOP pulse

QUIT

QT

Acknowledge error

TEACH Z

TZ

Accepts current position as real zero point. (P1 is
modified).
The data record indicator is set to 1.

TEACH Nxxx

TNxxx

Current position is written into set xxx using the
POSA command.
Not possible in "Reset mode".

BREAK

BK

Interrupts positioning or program step.

Example:

START N010 CR LF or SN 010 CR LF

Set 10 is executed

P211 Function

= 0

The functions I1 + I4, Teach N, I1 + I5 and Teach Z are enabled.

= 1

Teach Z is blocked; the data record indicator is set to 1 using I1 + I4 or
"Teach Z".

= 2

Teach N is blocked; the data record indicator is set to 1 using I1 + I5 or
"Teach N". (Teach Z is enabled)

= 3

The functions Teach N and Teach Z are blocked. With I1 + I4, Teach N, I1
+ I5 or Teach Z, the data record indicator is set to 1.

If commands are issued using RS232 and they cannot be executed (invalid
commands, missing password or COMPAX is busy), a warning is sent back.
Meaning:

E90

Syntax error; command not valid

E91

Command cannot be executed in this COMPAX operating mode.

E92

Function running, command cannot be executed

E93

Data record memory active, command cannot be executed

E94

Password missing

These warnings are not entered in status S18 (error history).

Transmitting
control
instructions

P211: blocking
and modifying the
teach in functions

Negative
command
acknowledge-
ment