MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Master Programming Level

ANN-LED Options Screen

Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-LED
option is selected, will display the following screen:

The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed to
annunciate Alarms, Troubles and Supervisories for Zones 00 through 09. The programming can be
changed using ANN-LED Address Screen 2.

Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate either Point (addressable device address) information or Zone information. Each press
of the 1 key will toggle the display between Point and Zone.

Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate only Alarms or Alarms, Troubles and Supervisories (ATS). Each press of the 2 key will
toggle the display between Alarms and ATS.

Pressing 3 while viewing ANN-LED Address Screen #2 will select the Point or Zone range to be
annunciated (refer to the tables in “ANN-RLED Zone Option - Alarm Only” on page 100 and
“ANN-RLED Point Option - Alarm Only” on page 101). Pressing the 3 key will display an addi-
tional screen where the range can be selected.

If Zone has been selected, and Alarms Only are to be annunciated, the 3 key will have no effect
since all zones can be displayed on only one ANN-LED module.

If Zone has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the
new screen will give the options of annunciating Zone 0 - 9 or 10 - 19. Two ANN-LED
modules are required to annunciate all zones in this configuration.

If Points has been selected, and Alarms Only are to be annunciated, the new screen will give
the options of annunciating Points 1 - 30 and 31 - 50. Two ANN-LED modules are required to
annunciate all points in this configuration.

If Point has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the
new screens will give the options of annunciating Points 1 - 10, 11 - 20, 21 - 30, 31 - 40 or 41 -
50. Five ANN-LED modules are required to annunciate all points in this configuration.

ANN-RLED Zone Option - Alarm Only

If Zone is selected as the module option, and the module is programmed to annunciate alarms only,
the first ten LEDs on the ANN-RLED module will display the system status information. The next
20 LEDs on the module will display the active/alarm status of each zone. The last 10 LEDs are not
used. The LED assignments for the ANN-RLED module will be as follows.

ANN-RLED Module

Alarm Silenced

NAC 1 Fault

NAC 2 Fault

Not Used

Not Used

Earth Fault

Battery Fault

Charger Fault

Disabled

Maintenance

Zone 00

Active/Alarm

Zone 01

Active/Alarm

Zone 02

Active/Alarm

Zone 03

Active/Alarm

Zone 04

Active/Alarm

Zone 05

Active/Alarm

Zone 06

Active/Alarm

Zone 07

Active/Alarm

Zone 08

Active/Alarm

Zone 09

Active/Alarm

Zone 10

Active/Alarm

Zone 11

Active/Alarm

Zone 12

Active/Alarm

Zone 13

Active/Alarm

Zone 14

Active/Alarm

Zone 15

Active/Alarm

Zone 16

Active/Alarm

Zone 17

Active/Alarm

Zone 18

Active Alarm

Zone 19

Active/Alarm

Not Used

Not Used

Not Used

Not Used

Not Used

PROGRAMMING

1=ANN-RLY OPTIONS

2=ANN-LED OPTIONS

ANN-BUS Screen #3

ANN-LED ADDR #

ZONES 00-09

ALARM, TRBL, SUPV

ANN-LED Address Screen #1

ANN-LED ADDR #

1=POINT/ZONE ZONE

2=ALARM/ATS ATS

3=RANGE ZN00-09

ANN-LED Address Screen #2