Section 3: programming, 1 programming data entry, Programming data entry – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 55

Advertising
background image

MS-9050 Series Manual — P/N 52413:G 4/14/2014

55

Section 3: Programming

3.1 Programming Data Entry

Programming can be accomplished using the MS-9050UD keypad or by connecting an optional
standard computer keyboard. The keyboard can be connected to the PS-2 connector J6 on the con-
trol panel main circuit board.

The information presented in this section refers to programming the MS-9050UD via the onboard
keypad. If an optional computer keyboard is connected to the MS-9050UD main circuit board, the
following table describes the keyboard keys which correspond to the onboard keypad keys.

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for

Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific

values or not used at all as indicated below:

Program feature

or option

Permitted in

UL 864? (Y/N)

Possible settings

Settings permitted in UL

864

Trouble Call Limit

N

Refer to “Trouble Call Limit (Dialer Runaway Prevention)” on
page 107.
Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble
to from 1 to 99 within a 24 hour period

Trouble Call Limit = 0
for unlimited Central Station
trouble calls

Remote Download

Y

Refer to “Remote Download” on page 150.
Remote Download - Proprietary No
Remote Download - Proprietary Yes

Remote Download
Proprietary Yes for
Proprietary Installations Only

Keypad Keys

Computer Keyboard Keys

1st Event

Home

CLR

Delete

ESC

Esc

RECALL

Insert

*

*

#

#

A - Z

A - Z

0 - 9

0 - 9



(on QZ key)

Space bar

/

/

ENTER

Enter

ACK/STEP

F1

SILENCE

F2

DRILL

F3

RESET

F4

Advertising