MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Master Programming Level

The Communication Format is determined by the type of receiver that the DACT is transmitting to.
Consult your Central Station for proper selection or consult our factory representatives. For any
format chosen, the control panel automatically programs all of the event codes.

Select the Communication Format by pressing the corresponding number key while viewing the
appropriate Comm Format screen. The following table describes each format:

Event Codes

Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following screen to be dis-
played:

Pressing the down arrow key allows viewing of all Events associated with the selected Communi-
cation Format. Pressing the number corresponding to the event displayed in each screen will dis-
play its default event code which can be customized by the programmer. For example, pressing 1
for Pull Station will display the following screen which allows the Event Code to be changed from
the default value.

The tables on the following pages list all of the Events and their default Event Codes for the various
Communication Formats.

Screen Selection

Communication Format Description

ADEMCO EXPRESS 4P1

4+1 Ademco Express Standard, DTMF, 1400/2300 ACK

ADEMCO EXPRESS 4P2

4+2 Ademco Express Standard, DTMF, 1400/2300 ACK

3P1S C18 A23

3+1 Standard 1800 Hz Carrier, 2300 Hz ACK

3P1E C18 A23

3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK

3P1S C19 A14

3+1 Standard 1900 Hz Carrier, 1400 Hz ACK

3P1E C19 A14

3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK

4P1S C18 A23

4+1 Standard 1800 Hz Carrier, 2300 Hz ACK

4P1E C18 A23

4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK

4P1S C19 A14

4+1 Standard 1900 Hz Carrier, 1400 Hz ACK

4P1E C19 A14

4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK

4P2S C18 A23

4+2 Standard 1800 Hz Carrier, 2300 Hz ACK

4P2E C18 A23

4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK

4P2S C19 A14

4+2 Standard 1900 Hz Carrier, 1400 Hz ACK

4P2E C19 A14

4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK

ADEMCO CONTACT ID

Contact ID, DTMF, 1400/2300 ACK

Table 3.2 Communication Formats

CENTRAL STATION

1=EVENT CODES

Primary/Secondary Screen #4

EVENT CODES

1=PULL STATION

2=MON-USER-DEF-1

3=WATERFLOW

Event Code Screen

PULL STATION 115