MS-9050 Series Manual — P/N 52413:G 4/14/2014

NFPA Standard-Specific Requirements

Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts

C.1 Central Station/Remote Station Transmitter: Connection

to FACP Dry Contacts

The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Sta-
tion/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value deter-
mined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter manu-
facturer’s manual for details.

Figure C.4 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter

Typical Central Station/Remote Station Transmitter Module

Typical Input Zone Triggers

MS-9050UDMain Circuit Board

Al

a

rm

Tr

ouble

*

Super

visory

*Note: The Trouble Relay is a fail-
safe relay. With power applied to
the FACP and no troubles in the
panel, the wiring should be
connected to the NO and C contacts
as indicated in the illustration.

ms9

0

5

0

UD

dryxm

it.

w

mf

Advertising